  A check valve can leak through its seat for the following reasons:  
       
  1 The valve is installed in an application in which it is not suitable.  
  Most swing check valves cannot be installed vertical with the flow passing though from above.  
       
  2 The valve was installed less than 10 pipe diameters away from upstream pipe fitting or pump. This results in turbulent flow, disc chatter and ultimately damage to the sealing surfaces.  
     
       
  3 The check valve is not closing fast enough allowing water hammer to slam the disc into the seat. Continued slamming has damaged the sealing surface preventing the valve from sealing fully.  
  Contact Velan Field Engineering Services to review options such as reducing the weight of the disc.  
     